Product Details:
Payment & Shipping Terms:
|
External Conductor: | Aluminium | Inner Conductor: | Aluminium Alloy |
---|---|---|---|
No. Of Wires: | 7pcs~73pcs | Cross-sectional Area: | 12mm²~900mm² |
Application: | Overhead Power System | Insulation: | No |
Sheath: | No | ||
High Light: | transmission conductor,bare overhead conductors |
Aluminium Stranded Bare Conductor Alloy-reinforced (ACAR) 16mm²~1250mm²
ACAR | IEC 61089 | ||||||||||
Diameter | Number of Wirers | Area | Linear | Rated | Max D.C. Resis- | ||||||
Code Number | Wire | Cond. | Al. | Alloy | Al. | Alloy | Total | Mass | strength | tance at 20℃ | |
mm | mm | mm | mm | mm2 | mm2 | mm2 | kg/km | kN | Ω/km | ||
16 | 1.76 | 5.28 | 4 | 3 | 9.73 | 7.30 | 17.0 | 46.6 | 3.85 | 1.7896 | |
25 | 2.20 | 6.60 | 4 | 3 | 15.2 | 11.4 | 26.6 | 72.8 | 5.93 | 1.1453 | |
40 | 2.78 | 8.35 | 4 | 3 | 24.3 | 18.3 | 42.6 | 116.5 | 9.25 | 0.7158 | |
63 | 3.49 | 10.5 | 4 | 3 | 38.3 | 28.7 | 67.1 | 183.5 | 14.38 | 0.4545 | |
100 | 4.40 | 13.2 | 4 | 3 | 60.8 | 45.6 | 106 | 291.2 | 22.52 | 0.2863 | |
125 | 2.97 | 14.9 | 12 | 7 | 83.3 | 48.6 | 132 | 362.7 | 27.79 | 0.2302 | |
160 | 3.36 | 16.8 | 12 | 7 | 107 | 62.2 | 169 | 464.2 | 35.04 | 0.1798 | |
200 | 3.76 | 18.8 | 12 | 7 | 133 | 77.8 | 211 | 580.3 | 43.13 | 0.1439 | |
250 | 4.21 | 21.0 | 12 | 7 | 167 | 97.2 | 264 | 725.3 | 53.92 | 0.1151 | |
250 | 3.04 | 21.3 | 18 | 19 | 131 | 138 | 269 | 742.2 | 60.39 | 0.1154 | |
315 | 3.34 | 23.4 | 30 | 7 | 263 | 61.3 | 324 | 892.6 | 60.52 | 0.0916 | |
315 | 3.42 | 23.9 | 18 | 19 | 165 | 174 | 339 | 935.1 | 76.09 | 0.0916 | |
400 | 3.76 | 26.3 | 30 | 7 | 334 | 77.8 | 411 | 1133.5 | 75.19 | 0.0721 | |
400 | 3.85 | 27.0 | 18 | 19 | 210 | 221 | 431 | 1187.5 | 95.58 | 0.0721 | |
450 | 3.99 | 27.9 | 30 | 7 | 375 | 87.6 | 463 | 1275.2 | 84.59 | 0.0641 | |
450 | 4.08 | 28.6 | 18 | 19 | 236 | 249 | 485 | 1335.9 | 107.52 | 0.0641 | |
500 | 4.21 | 29.4 | 30 | 7 | 417 | 97.3 | 514 | 1416.9 | 93.98 | 0.0577 | |
500 | 4.31 | 30.1 | 18 | 19 | 262 | 277 | 539 | 1484.3 | 119.47 | 0.0577 | |
560 | 4.45 | 31.2 | 30 | 7 | 467 | 109 | 576 | 1586.9 | 105.26 | 0.0515 | |
560 | 3.45 | 31.0 | 54 | 7 | 504 | 65.4 | 570 | 1571.9 | 101.54 | 0.0516 | |
630 | 3.71 | 33.4 | 42 | 19 | 454 | 205 | 660 | 1820.0 | 130.25 | 0.0458 | |
630 | 3.79 | 34.1 | 24 | 37 | 271 | 417 | 688 | 1897.5 | 160.19 | 0.0458 | |
710 | 3.94 | 35.5 | 42 | 19 | 512 | 232 | 743 | 2051.2 | 146.78 | 0.0407 | |
710 | 4.02 | 36.2 | 24 | 37 | 305 | 470 | 775 | 2138.4 | 180.53 | 0.0407 | |
800 | 4.18 | 37.6 | 42 | 19 | 577 | 261 | 838 | 2311.2 | 165.39 | 0.0361 | |
800 | 4.27 | 38.4 | 24 | 37 | 344 | 530 | 873 | 2409.5 | 203.41 | 0.0361 | |
900 | 4.43 | 39.9 | 42 | 19 | 649 | 294 | 942 | 2600.1 | 186.06 | 0.0321 | |
900 | 3.66 | 40.2 | 54 | 37 | 567 | 388 | 955 | 2638.4 | 199.54 | 0.0321 | |
1000 | 3.80 | 41.8 | 72 | 19 | 816 | 215 | 1032 | 2849.1 | 190.94 | 0.0289 | |
1000 | 3.85 | 42.4 | 54 | 37 | 630 | 432 | 1061 | 2931.6 | 221.71 | 0.0289 | |
1120 | 4.02 | 44.2 | 72 | 19 | 914 | 241 | 1155 | 3191.0 | 213.85 | 0.0258 | |
1120 | 4.08 | 44.9 | 54 | 37 | 705 | 483 | 1189 | 3283.4 | 248.32 | 0.0258 | |
1250 | 4.25 | 46.7 | 72 | 19 | 1020 | 269 | 1289 | 3561.4 | 238.68 | 0.0231 | |
1250 | 4.31 | 47.4 | 54 | 37 | 787 | 539 | 1327 | 3664.5 | 277.14 | 0.0231 | |
1400 | 4.50 | 49.4 | 72 | 19 | 1143 | 302 | 1444 | 3988.8 | 267.32 | 0.0207 |
Application
The bare conductor:AAC,AAAC,ACSR,AACSR,ACAR and Galvanized steel wire, are used in overhead electrical power transmission and distribution lines with various grade voltage.
Construction: Bare aluminum alloy 1350-H19 wires, concentrically stranded around a Class A galvanized coated steel core wire. ACSR consists of a galvanized steel core of 1 wire, 7 wires, 19 wires etc. surrounded by concentric layers of aluminum wire.
Standards
Our Bare conductor can meet or exceedthe item of cable international standards, such as:IEC 61089, BS 215 part1(AAC), BS 215 part2, BS 324201 (AAAC), DIN 48201 part 5 (AAC), DIN 48204, ASTM B231(AAC), ASTM B232(ACSR), BS EN 50182, BS EN 50183(AAAC), GB/T 1179-2008. Also we accept the OEM and the new design cable as customers.
Specification
1. Aluminum conductor
2. Concentric-Lay-Stranded
3. Coated Steel Reinforced
4. ASTM,BS,CSA,DIN,IEC etc. Standards
Following the American Standards ( ASTM )
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341 Aluminum-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)
Type | Description | No. of Wire | Section Area (mm2) |
AAC | All Aluminum Conductor | 7~127 | 16~1500 |
AAAC | All Aluminum Alloy Conductor | 7~91 | 17~1300 |
ACSR | Aluminum Conductors Steel Reinforced |
7~103 | 16~1250 |
AACSR | Aluminum Alloy Conductors Steel Reinforced |
7~103 | 16~1250 |
ACAR/AW | Aluminum Conductors Aluminum Alloy Reinforced |
7~103 | 16~1250 |
ACSW/S | Aluminum Conductors Aluminum Clad Steel Wire/Strand |
7~103 | 16~1250 |
GSW | Galvanized Steel Wire | 3/2.64~37/4.55 | 16.41~765.99 |