Technical Overview of 31 Core 240mm Aluminum XLPE Power Cables
A 3+1 core power cable rated 600/1000 V and sized 3x240+1x120 mm² is designed for systems that require a separate grounding conductor. The cable uses XLPE insulation and a PVC outer sheath and is manufactured to IEC 60502-1. It is intended for industrial power distribution and large lighting installations operating at 1 kV and below.
The cable’s 3+1 configuration consists of three main phase conductors and one ground conductor, a layout intended to meet specific grounding-performance requirements. Its conductors are stranded to IEC 60228 Class 2, which specifies conductor construction for conductivity and mechanical flexibility. Non-hygroscopic fillers and binder tapes keep the internal assembly compact and are intended to limit moisture ingress, supporting stability in long-term operation.
The insulation is cross-linked polyethylene, or XLPE, while the outer sheath is polyvinyl chloride, or PVC. The cable has an overall diameter of 55.3 mm and weighs 8,500 kg/km. Its rated voltage is 600/1000 V (U0/U).
| Item | Specification |
|---|---|
| Rated voltage (U0/U) | 600/1000 V |
| Number of cores | 3+1 |
| Phase conductor cross-section | 240 mm² |
| Ground conductor cross-section | 120 mm² |
| Insulation material | XLPE |
| Outer sheath material | PVC |
| Overall diameter | 55.3 mm |
| Cable weight | 8,500 kg/km |
| Current capacity in air | 480 A |
| Current capacity in soil | 500 A |
| Operating temperature range | -15°C to +90°C |
| Maximum short-circuit temperature | 250°C |
The cable is used in power systems with rated voltages up to 1 kV. Its XLPE insulation is designed to provide electrical insulation and thermal stability, with a maximum continuous operating temperature of 90°C and a short-circuit temperature limit of 250°C. In air, the cable’s current capacity is 480 A; in soil, it is 500 A.
The ratio of phase-conductor to ground-conductor cross-section—240 mm² to 120 mm²—is intended to balance material use with an effective ground-return path under fault conditions. The configuration is intended to maintain an effective ground-return path under fault conditions, a factor relevant to protection operation in industrial equipment and lighting systems.
The 55.3 mm overall diameter is a key factor in cable selection and installation. When designing cable trays, conduits, or direct-burial trenches, sufficient bending-radius space should be reserved to reduce the risk of insulation damage or concentrated mechanical stress. The cable’s operating temperature range is -15°C to +90°C, with a maximum short-circuit temperature of 250°C.