Product Details:
Payment & Shipping Terms:
|
Rated Voltage: | 6/10kV | Insulation Color: | Nature Color |
---|---|---|---|
Core Mark: | Color Strip | Core: | Single Core Or Three Core |
Outer Sheath Color: | Black Or As Per Request | Cable Mark: | Ink Printing Or Embossing |
Cable Drum Length: | 300-500 Meter Per Drum | Metal Screen: | Copper Tape Screen (CTS) |
High Light: | xlpe insulation cable,xlpe electrical cable |
Medium Voltage Copper Conductor XLPE Insulated Power Cable professional Manufacturer
Description:
6/10kv XLPE Insulated cables
CU/XLPE/ PVC, IEC 60502
IEC 60502, IEC 60228, GB/T 12706.1-2008.
CE, CCC, KEMA. ISO
Constructions
Conductor : Compact stranded copper conductor, Cl.2 as per IEC 60228
Conductor Screen: Semi-conductor
Insulation : XLPE(cross-linked polyethylene) rated at 90 ℃
Insulation Screen: Semi-conductor
Screen : Copper tape
Sheath : PVC type ST2 to IEC 60502, black
Note:
Insulation color as per standards or customer requirement
Applications
Underground Cable Laying, Construction Building.
Standards
International: IEC 60502, IEC 60228
China: GB/T 12706.1-2008
Other standards such as BS,DIN and ICEA upon request
Technical data
Rated voltage: 6/10kv
Maximum Conductor Temperature: under normal (90 ℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0℃
Min. Bending Radius: single core cable 20(d+D)±5%
Multi-core cable 15(d+D)±5%
Certificates
CE, RoHS, CCC, KEMA and more others at request
Technical Specifications
Nom. Cross-section of conductor | Strands No./Dia. Of Conductor | Insulation Thickness | Sheath Thickness | Approx. O.D. |
Approx. Weight |
Max. D.C Resistance of Conductor (20 ℃) | Testing Voltage A.C | Current Rating | |
mm2 | pc/mm | mm | mm | (mm) | kg/km | Ω /km | kV/5min | In air (A) | In soil(A) |
1 × 25 | 7/2.14 | 3.4 | 2 | 20.0 | 598 | 0.727 | 21 | 140 | 150 |
1 × 35 | 7/2.52 | 3.4 | 2 | 22.0 | 719 | 0.524 | 21 | 175 | 180 |
1 × 50 | 10/2.52 | 3.4 | 2 | 23.0 | 884 | 0.387 | 21 | 205 | 215 |
1 × 70 | 14/2.52 | 3.4 | 2 | 24.0 | 1097 | 0.268 | 21 | 260 | 265 |
1 × 95 | 19/2.52 | 3.4 | 2 | 26.0 | 1378 | 0.193 | 21 | 315 | 315 |
1 × 120 | 24/2.52 | 3.4 | 2 | 28.0 | 1658 | 0.153 | 21 | 365 | 360 |
1 × 150 | 30/2.52 | 3.4 | 2 | 30.0 | 1967 | 0.124 | 21 | 415 | 405 |
1 × 185 | 37/2.52 | 3.4 | 2 | 31.0 | 2335 | 0.0991 | 21 | 475 | 455 |
1 × 240 | 48/2.52 | 3.4 | 2 | 34.0 | 2908 | 0.0754 | 21 | 565 | 530 |
1 × 300 | 61/2.52 | 3.4 | 2 | 36.0 | 3507 | 0.0601 | 21 | 645 | 595 |
1 × 400 | 61/2.97 | 3.4 | 2.5 | 39.0 | 4503 | 0.0470 | 21 | 750 | 680 |
1 × 500 | 61/3.23 | 3.4 | 2.5 | 42.0 | 5479 | 0.0366 | 21 | 865 | 765 |
1 × 630 | 61/3.50 | 3.4 | 2.5 | 48.0 | 6952 | 0.0283 | 21 | 990 | 860 |
1 × 800 | 91/3.20 | 3.4 | 2.6 | 52.0 | 7120 | 0.0221 | 21 | 1140 | 950 |
1 × 1000 | 91/3.75 | 3.4 | 2.8 | 57.0 | 10500 | 0.0176 | 21 | 1250 | 1040 |
3 × 25 | 7/2.14 | 3.4 | 2.3 | 41.0 | 895 | 0.727 | 21 | 120 | 125 |
3 × 35 | 7/2.52 | 3.4 | 2.4 | 44.0 | 2293 | 0.524 | 21 | 145 | 155 |
3 × 50 | 10/2.52 | 3.4 | 2.5 | 46.0 | 2812 | 0.387 | 21 | 175 | 180 |
3 × 70 | 14/2.52 | 3.4 | 2.6 | 50.0 | 3508 | 0.268 | 21 | 220 | 220 |
3 × 95 | 19/2.52 | 3.4 | 2.7 | 53.0 | 4402 | 0.193 | 21 | 265 | 265 |
3 × 120 | 24/2.52 | 3.4 | 2.8 | 56.0 | 5319 | 0.153 | 21 | 305 | 300 |
3 × 150 | 30/2.52 | 3.4 | 2.9 | 59.0 | 6309 | 0.124 | 21 | 350 | 340 |
3 × 185 | 37/2.52 | 3.4 | 3.0 | 62.0 | 7319 | 0.0991 | 21 | 395 | 380 |
3 × 240 | 48/2.52 | 3.4 | 3.2 | 68.0 | 9218 | 0.0754 | 21 | 470 | 435 |
3 × 300 | 61/2.52 | 3.4 | 3.4 | 72.0 | 11159 | 0.0601 | 21 | 535 | 485 |
3 × 400 | 61/2.97 | 3.4 | 3.6 | 81.0 | 15107 | 0.0470 | 21 | 610 | 520 |
Ordering Advice
Rated Voltage
Application Standard: IEC/BS/UL/GB
Number of Cores
Conductor Size & Construction
Type of Insulation
Armored or unarmored. If armor, the armor type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
PACKING AND SHIPPING
We are capable of meeting the strictest delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self-adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.