Product Details:
Payment & Shipping Terms:
|
Application: | Industrial | Type: | Low Voltage |
---|---|---|---|
Insulation: | XLPE | Rated Voltage: | 0.6/1 KV |
Test Voltage: | 3.5 KV For 5 Minutes | Reference Standard: | IEC60502-1 |
High Light: | PVC Insulated Power Cable,PVC Electrical Cable |
0.6/1kV XLPE Insulated Power Cable Muti-Cores for Power Transmission KEMA
Application
These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.
Construction
Conductor: Plain annealed copper, class 1 solid or class 2 stranded acc. to IEC 60228.
Flexible class 5 or tinned conductor could be offer upon request.
Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.
Outer Sheath: PVC ST8 (90°C) of IEC 60502-1.
Outer Sheath Colour: Black or other color as per customer request.
Electrical Characteristics
Recommended rated voltages U0
Highest system voltage(Um) (kV) | Rated voltage (U0) (kV) | |
Categories A and B | Category C | |
1,2 | 0,6 | 0,6 |
Routine test voltages
Rated voltage U0 (kV) | 0,6 |
Test voltage (kV) | 3,5 |
Maximum conductor temperatures for different types of insulating compound
Maximum conductor temperature (°C) | |
Normal operation | Short-circuit (5 s maximum duration) |
90 | 250 |
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Installation Refference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 70
Reference Standards
Design: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC 60332-1, BS EN60332-1