Product Details:
Payment & Shipping Terms:
|
| Product Name: | Low Smoke Metro Tunnel PVC Cable PVC Insulated Cable | Application: | Metro Tunnel And Underground Ventilation Power Supply |
|---|---|---|---|
| Conductor: | Class 2 Stranded Bare Copper | Insulation: | Low Smoke Halogen Free Compound, 90 Deg C |
| Rated Voltage: | 0.6/1 KV | Core Configuration: | 5 X 16 Mm2 |
| Halogen Content: | IEC 60754-1 Below 0.5 Percent | Smoke Density: | IEC 61034-2, Transmittance Above 70 Percent |
| Sheath Compound: | Low Smoke Halogen Free Compound LSHF-90 | Standard: | IEC 60502-1, IEC 60332-3-24 |
| Highlight: | Low smoke metro tunnel PVC cable,Halogen free 5x16mm2 1kV cable,IEC 60332-3-24 tunnel cable |
||
Tunnel environments are the hardest case for cable fire performance, because smoke has nowhere to disperse and evacuation distances are long. This five core cable combines halogen free insulation and sheath so that no part of the construction contributes acid gas, while the low smoke compound keeps transmittance high enough for tunnel lighting and signage to stay visible.
Key Features| Parameter | Specification |
|---|---|
| Conductor | Class 2 stranded bare copper |
| Cross Section | 5 x 16 mm2 |
| Rated Voltage | 0.6/1 kV |
| Insulation | Low smoke halogen free compound, 90 deg C |
| Sheath | LSHF-90 compound, black |
| Smoke Density | IEC 61034-2, transmittance above 70 percent |
| Halogen Content | IEC 60754-1 below 0.5 percent |
| Fire Resistance Option | IEC 60331-21 available on request |
| Standard | IEC 60502-1, IEC 60332-3-24 |
| Approx Weight | 1520 kg/km |
Construction summary: Class 2 stranded bare copper with Low smoke halogen free compound, 90 deg C, rated 0.6/1 kV and sheathed in Low Smoke Halogen Free Compound LSHF-90. The 5 x 16 mm2 layout is supplied in coil, plywood reel or steel drum according to project handling requirements.
ApplicationsThe cable feeds ventilation fans, sump pumps, lighting circuits and sign power inside road and metro tunnels. Using a single five core cable for three phase, neutral and earth reduces the number of pulls in congested tunnel trays, which matters when installation windows are limited to night possessions.
Does halogen free insulation matter as much as the sheath? Yes. If the sheath is halogen free but the insulation is standard PVC, a fire inside the cable still releases acid gas. This construction uses halogen free compounds for both layers, so total halogen content stays below 0.5 percent.
Can a fire resistant version be supplied for escape circuits? Yes. The same five core design is available with mica tape and a fire resistant compound that meets IEC 60331-21 for 90 minutes at 750 deg C, intended for emergency lighting and ventilation control circuits.
How does the five core layout affect derating? Five loaded cores in air are derated to roughly 0.75 of the four core value. For a 16 mm2 copper construction this gives about 66 A per phase in free air at 30 deg C, and site conditions may require further correction.
Installation GuidanceCable is wound on export grade wooden drums or coiled in polyethylene wrapped rolls, with drum flange marking showing type, size, length and batch number. Each batch is routine tested for conductor resistance, insulation resistance and high voltage withstand, and a mill test certificate is issued with the shipping documents. Standard packing suits 20 foot and 40 foot containers, and drum sizes are matched to the ordered length to avoid unused freight space.