Product Details:
Payment & Shipping Terms:
|
| Product Name: | Sunlight Resistant PVC Wire 6mm2 PVC Insulated Wire | Application: | Open Air Cable Tray And Rooftop Equipment Wiring |
|---|---|---|---|
| Conductor: | Class 5 Fine Stranded Bare Copper | Insulation: | Sunlight Resistant PVC, 90 Deg C |
| Rated Voltage: | 0.6/1 KV | Core Configuration: | 1 X 6 Mm2 |
| UV Resistance: | ISO 4892-3, 2000 H With Elongation Retention Above 80 Percent | Weather Resistance: | Outdoor Rated, Humid And Ozone Tested |
| Sheath Compound: | Sunlight Resistant PVC Compound SR-90 | Standard: | IEC 60227-3, IEC 60332-1 |
| Highlight: | Sunlight resistant PVC wire 6mm2,Outdoor tray single core cable,UV stable class 5 copper wire |
||
Rooftop and open air cable trays reach surface temperatures far above ambient because of solar gain, and the combined effect of heat and ultraviolet light is what destroys ordinary PVC wire on exposed installations. This single core wire carries a 90 deg C sunlight resistant compound verified over 2000 hours of UV exposure, so it can be laid in open trays without conduit covers.
Key Features| Parameter | Specification |
|---|---|
| Conductor | Class 5 fine stranded bare copper |
| Cross Section | 1 x 6 mm2 |
| Rated Voltage | 0.6/1 kV |
| Insulation | Sunlight resistant PVC, 90 deg C |
| Colour Range | Black, brown, blue, yellow-green |
| UV Test | ISO 4892-3, 2000 h with elongation retention above 80 percent |
| Surface Temperature | Rated for 70 deg C sheath surface in direct sun |
| Flex Rating | Class 5, 5 times diameter bend radius |
| Standard | IEC 60227-3, IEC 60332-1 |
| Approx Weight | 72 kg/km |
Construction summary: Class 5 fine stranded bare copper with Sunlight resistant PVC, 90 deg C, rated 0.6/1 kV and sheathed in Sunlight Resistant PVC Compound SR-90. The 1 x 6 mm2 layout is supplied in coil, plywood reel or steel drum according to project handling requirements.
ApplicationsThe wire is used on rooftop HVAC equipment, telecom cabinet supplies and open tray runs on industrial roofs. Because the insulation can be exposed directly to sun, projects avoid the cost of UV resistant conduit and the derating that comes with enclosed conduit, while still retaining flexibility for final connections to vibrating rooftop units.
Can the wire be laid without conduit in sun? Yes. The compound is designed for direct exposure and tested for 2000 hours of xenon arc radiation with elongation retention above 80 percent, which corresponds to well over a decade of outdoor service in most climates.
How much does solar gain affect current capacity? Surface temperature on a black tray in full sun can reach 70 deg C. Apply the correction factor for 70 deg C ambient rather than the nominal 30 deg C air value, which typically reduces capacity by around 25 percent.
Is the wire suitable for marine or coastal sites? For coastal sites a tinned conductor option is recommended to limit copper oxidation at terminations, while the sheath itself resists salt spray and UV in equal measure.
Installation GuidanceCable is wound on export grade wooden drums or coiled in polyethylene wrapped rolls, with drum flange marking showing type, size, length and batch number. Each batch is routine tested for conductor resistance, insulation resistance and high voltage withstand, and a mill test certificate is issued with the shipping documents. Standard packing suits 20 foot and 40 foot containers, and drum sizes are matched to the ordered length to avoid unused freight space.