Product Details:
Payment & Shipping Terms:
|
Size: | 1.5sqmm~800sqmm | Conductor Type: | Copper |
---|---|---|---|
Core NO.: | Four | Sheath Color: | Orange |
Working Temperature: | 90℃ | Sample: | 20cm For Free Of Charge |
High Light: | fire retardant cable,fire proof cable |
0.6/1kV Single Core Fire Resistant Power Cable 1.5 sqmm ~ 800 sqmm IEC 60331
Construction: Cu/Mica/XLPE/LSZH/SWA/LSZH
(1) Conductor: Plain annealed copper (class 2, normal
stranded or compact stranded)
(2) Fire barrier: Mica tape
(3) Insulation: XLPE
(4) Filler, binder and inner covering: PP, PET, LSZH
(5) Armour: Steel wire
(6) Outer sheath: LSZH
PVC Insulated Cable is used as power distribution and transmission line at rated voltage 0.6/1KV.
Used outside as energy utility and lighting cables, in cable ducts, under ground, under normal and salty water if specially made.
Specifications
1.electric wire and cable
2.Over 20years professional experience
3.reliable repution&famous brand RMJT
1). Rated voltage U0/U 300/500V and 450/750V.
2). The long-time permissible temperature of cable: BV-105 below 105°C,and the other below 70°C.
3). Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160°c.
4). The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0°c.
5). The bend radius: the external diameter of cable <25mm, and the bend radius is above 4 times of the external diameter of
cable. And the other is above 6 times of the external diameter of cable.
6). Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame.
7). Light weight, perfect bending properties, installed and maintained easily and conveniently.
8). Insulation sheath material and color: PVC in red, black, blue or any color as required.
9). Type: Single or twin cables with different colors Provides OEM according to requests of customer.
Standards: BS 7846; IEC 60331; BS 6387
Construction: Cu/Mica/XLPE/LSZH/SWA/LSZH
(1) Conductor: Plain annealed copper (class 2, normal
stranded or compact stranded)
(2) Fire barrier: Mica tape
(3) Insulation: XLPE
(4) Filler, binder and inner covering: PP, PET, LSZH
(5) Armour: Steel wire
(6) Outer sheath: LSZH
Cable identification
- Cores: Red, yellow, blue, black, green/yellow (by color tape, except green-yellow core)
- Outer sheath: orange or as order
Characteristics
- Voltage rate: 0.6/1kV
- Maximum conductor temperature: 900C in normal operation; 2500C in short-circuit for 5s max.
- Minimum bend radius: 12xD (twelve times overall diamerter of cable)
- Fire resistant: IEC 60331; BS 6387
- Flame retardant: BS EN 60332-1; IEC 60332-1
- Corrosive and acid gas: BS 7846; BS 50267-2-1; IEC 60754-1&2
Smoke emission: BS 7846; BS EN 50268-2; IEC 61034-2
Notes: * All conductor in accordance with IEC 60228. Compacted conductor (C.C) or non-compacted depend on order.
• Besides the above mentioned list we can also provide other sizes depending on customer’s requirement.
Installation
1. The installation temperature should not over 20℃, If the ambient temperature is lower than 0℃, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.
3. After installantion, the cable should with stand voltage test for 15min. 3.5kv D.C.
Technical parameter:
Temperature range in motion -5°C till +70°C
fixed -20°C till +70°C
Operating temperature short circuit °C 250
Short circuit time max. [sec] 5
Bending radius min. x diameter 15
Flammability standard EN 60332-1-2