Product Details:
Payment & Shipping Terms:
|
Name: | Low Smoke Halogen Free Cable | Application: | In Tunnels And In Ducts Used For Electric Transmission And Distribution Control Systems |
---|---|---|---|
Size: | Custom Made | Rated Voltage: | 0.6/1kV |
Free Sample: | Yes | Color: | Orange Or Customized |
Standard: | IEC60754, IEC61034-1 60331 | Type: | Lszh Power Cable |
Corporation: | Shenghua Group | Brand: | Sh Cable |
Highlight: | low smoke halogen free cable,lszh power cable |
0.6/1kV Low Smoke Halogen Free Cable / Lszh Power Cable Indoor Installation
Low Smoke Halogen Free CableApplications:
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Insulation: Cross linked polyethylene compound is insulated over the conductors by extrusion process.The raw materials and thicknesses of Insulation are maintained as per standards and conform to IEC60502/BS7870 Standards as the case may be.
XLPE:Insulated Power Cable are identified either by colour or by numbers as follows:
No. of cores Identification
Old Colour coding New Colour coding as per different customers. Normally the color as below:
1 Red or Black Brown or Blue
2 Red & Black Brown, Blue
3 Red, Yellow Blue Brown, Black, Grey
4 Red, Yellow, Blue & Black Blue, Brown, Black, Grey
5 Red, Yellow, Blue, Black, Y/G Blue, Brown, Black, Grey & Y/G
Armour : Single core cables are armored with Aluminium Wires or Aluminum Tape armored based on requirement.
Three core: steel wire armored or Steel tape armored.
Outer sheath : Polyene Hydrogen Sheath , LSHO
Standards
International: IEC 60502, IEC 60227 IEC 60331, IEC 61034 60332
China: GB/T 12706-91 GB306.1-2001, GB/T18380.3-2001
Other standards such as BS,DIN and ICEA upon request
Low Smoke Halogen Free Cable Technical data
Rated voltage: 0.6-KV
Max. Conductor Temp.:normal (90℃), short circuit no more than 5 s (the highest temperature of conductor shall no more than 250°C )
Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0°C
Min. Bending Radius: single core cable 20(d+D)±5% ,Multi-core cable 15(d+D)±5%
Type | Description | Cores | Nominal Cross Section |
WDZA-YJY WDZB-YJY WDZC-YJY |
Copper conductor/XLPE insulation Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJY23 WDZB-YJY23 WDZC-YJY23 | Copper conductor/XLPE insulation/Steel Tape Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJY33 WDZB-YJY33 WDZC-YJY33 | Copper conductor/XLPE insulation/Steel Wire Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJLY WDZB-YJLY WDZC-YJLY | Aluminum conductor/XLPE insulation Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJLY23 WDZB-YJLY23 WDZC-YJLY23 | Aluminum conductor/XLPE insulation/Steel Tape Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJLY33 WDZB-YJLY33 WDZC-YJY33 | Aluminum conductor/XLPE insulation/Steel Wire Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |