Product Details:
Payment & Shipping Terms:
|
Core No.: | 4 Core | Insulation Color: | Yellow,Blue Red Green Or As Per Request |
---|---|---|---|
Standard: | IEC 60502-1,IEC 60228 | Outer SheathIdentification: | Ink Printing Or Embossing |
Drum Length: | 500 M Or As Per Request | Conductor Size: | 1.5mm2-630mm2 |
Corporation: | Shenghua Group | Brand: | Sh Cable |
Highlight: | low smoke halogen free cable,low smoke zero halogen wire |
4 Cores No Halogen Fire Retardant Fire Resisting Power Cable 0.6/1kV IEC60332
XLPE insulated power cable has a number of advantages over paper insulated and PVC insulated cable. XLPE power cable has high electric strength, mechanical strength, high-ageing resisting, environmental stress resisting anti-chemical corrosion, and it is simple construction, using convenient and higher operating of long term temperature. It can be laid with no drop restriction.
The flame-retardant and non-flame retardant LSZH XLPE cable can be manufactured with three technologies (peroxide, silane and irradiation cross-linking). The flame-retardant cable covers all kinds of low-smoke low-halogen low-smoke halogen free, and non-smoke non-halogenated and three classes of A,B,C.
Constructions
Conductor | : | Plain Annealed, Stranded Circular Non – Compacted or Circular Compacted or Shaped Copper |
---|---|---|
Fire Barrier | : | Mica Tape |
Insulation | : | XLPE (For FR-200) or LSOH (For FR-300) |
Sheath | : | LSOH |
Standards
International: IEC 60502, IEC 60228
China: GB/T 12706.1-2008
Other standards such as BS,DIN and ICEA upon request
Technical data
Rated voltage: 0.6/1kV
Max. Conductor Temp.: normal (90℃), short circuit no more than 5 s (160℃ when section-area below 300mm2, 140℃ when section-area above 300mm2)
Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0℃
Min. Bending Radius: single core cable 20(d+D)±5%
Multi-core cable 15(d+D)±5%
Certificates
CE, RoHS, CCC, KEMA and more others at request
Ordering Advice
Rated Voltage
Application Standard: IEC/BS/UL/GB
Number of Cores
Conductor Size & Construction
Type of Insulation
Armored or unarmored. If armor, the armor type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
Technical Specifications:
Nom. Cross-section of conductor | Strands No./Dia. of Conductor | Insulation Thickness | Sheath Thickness | Approx. O.D. |
Approx .Weight |
Max. D.C Resistance of Conductor (20 ℃) | Testing Voltage A.C | Current Rating | |
mm2 | pc/mm | mm | mm | Lower Limit (mm) | kg/km | Ω /km | kV/5min | In air (A) | Direct In soil(A) |
4 × 4 | 1/2.25 | 0.7 | 1.8 | 13.0 | 253 | 4.61 | 3.5 | 34 | 45 |
4 × 6 | 1/2.76 | 0.7 | 1.8 | 14.0 | 337 | 3.08 | 3.5 | 43 | 57 |
4 × 10 | 7/1.38 | 0.7 | 1.8 | 17.0 | 501 | 1.83 | 3.5 | 60 | 77 |
4 × 16 | 7/1.78 | 0.7 | 1.8 | 20.0 | 778 | 1.15 | 3.5 | 83 | 105 |
4 × 25 | 7/2.14 | 0.9 | 1.8 | 23.0 | 1160 | 0.727 | 3.5 | 105 | 125 |
4 × 35 | 7/2.52 | 0.9 | 1.8 | 25 | 1554 | 0.524 | 3.5 | 125 | 155 |
4 × 50 | 10/2.52 | 1.0 | 1.8 | 23 | 2148 | 0.387 | 3.5 | 160 | 185 |
4 × 70 | 14/2.52 | 1.1 | 1.8 | 27 | 2928 | 0.268 | 3.5 | 200 | 225 |
4 × 95 | 19/2.52 | 1.1 | 1.9 | 31 | 3854 | 0.193 | 3.5 | 245 | 270 |
4 × 120 | 24/2.52 | 1.2 | 2.0 | 33 | 4925 | 0.153 | 3.5 | 285 | 310 |
4 × 150 | 30/2.52 | 1.4 | 2.2 | 38 | 6238 | 0.124 | 3.5 | 325 | 345 |
4 × 185 | 37/2.52 | 1.6 | 2.3 | 42 | 7562 | 0.0991 | 3.5 | 375 | 390 |
4 × 240 | 48/2.52 | 1.7 | 2.5 | 47 | 9836 | 0.0754 | 3.5 | 440 | 450 |
4 × 300 | 61/2.52 | 1.8 | 2.6 | 52 | 12550 | 0.0601 | 3.5 | 505 | 515 |
4 × 400 | 61/2.97 | 2.0 | 3.1 | 66 | 15929 | 0.0470 | 3.5 | 570 | 575 |
Packing and Shipping
We are capable of meeting the strictest delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self-adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.
After-service commitment:
Shanghai Shenghua Cable (Group) possesses Shenghua tenet "Strive for the Best Enterprise, Produce the Best Product, Provide the Best Service, Establish the Best Brand", insists the policy of quality first, endeavors to achieve high quality and zero defect of goods. Therefore, every client could fully benefit from Shenghua Cable's superior quality and faultless service. Meanwhile, we observe Shenghua spirit of "Do Best, Mutually Win", wish to establish long-term and stable relationship with every client. Hereby, we guarantee that:
1. Customer is God. We will cherish every client, every cooperation by heart.
2. Free pre-sales service. We will provide best proposal for each client.
3. Good sales service. We will provide free relative product operation, maintenance tips and installation commissioning technical advisory service when establish cooperation relationship with clients.
4. Thoughtful after sales service. Our product are warranted by PICC (People's Insurance Company of China). We will provide free maintaining and debugging within 12 month after installation(except for the wrong using).
5. We guarantee solve your problems within 24 hours in Shanghai, 72 hours for other district.
6. 24 hours hot-line telephone service. We will appoint professional person answer your question timely.
We always firmly believe that " Quality is life line, Service is laissez-passer", which will make us more closer and tight!
Shanghai Shenghua Cable (Group) Co., Ltd.