Quintuple Aerial Bundled Cable 0.6/1kV for Overhead Power Lines
Aerial bundled cables (also aerial bundled conductors or simply ABC) are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. This contrasts with the traditional practice of using uninsulated conductors separated by air gaps. This variation of overhead power lines utilizes the same principles as bundled conductors, except that they are closer together to the point of touching but each conductor is surrounded by an insulating layer (except for the neutral line).
Design.
1 Aluminium conductor with increased breaking load, round stranded compressed (RM)
2 Core insulation (XPLE black, UV-resistant, not flame retardant); 2 up to 4 cores of equal cross section are stranded together in left-hand lay, additionally 1 or 2 cores of reduced cross section can be co-stranded
Application
Can be used for fixed installation as overhead power lines up to 1.000 V incl.
Not suitable for direct burial.
This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140 It is not flame retardant. But this could be if requested change to a flame retardant cable
Specification
(1). BS Standard ABC Cable
(2). CCC,ISO9001,ISO14001, best quality control.
(3). More than 20 years Proffessional experience, best service.
(4). We are a factory manufacturing ,Best production capability,best Price.
(5). 100% QC inspection before shippment.
Introduction
ABC Cable are overhead power lines using several insulated phase conductors bundled tightly together,
usually with a bare neutral conductor. They can improves safety and reliance of electrified wire netting.
Standard
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Applications:
TO supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting.
For service at 600 volt or lower at a conductor temperature of 75 maximum.
Schedule of technical particulars
Phase conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
Number of cores | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Minimum number of wires | 6 | 6 | 6 | 12 | 15 | 15 | 30 | 30 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.4 | 1.4 | 1.6 | 1.6 | 1.8 | 2.0 |
Diameter of insulated core | mm | 8.5 | 9.5 | 11.2 | 13.0 | 15.1 | 16.6 | 18.4 | 20.6 |
Max. DC resistance at 20℃ | ohm/km | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 |
Current rating at still wind, ambient | A | 84 | 104 | 129 | 167 | 209 | 246 | 283 | 332 |
temperature=30℃ | |||||||||
Conductor temperature=75℃ | |||||||||
Messenger conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
Minimum number of wires | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
Diameter of insulated core | mm | 8.5 | 8.5 | 9.5 | 11.2 | 13.1 | 13.1 | 15.1 | 16.6 |
Max. DC resistance at 20℃ | ohm/km | 1.312 | 1.312 | 0.943 | 0.693 | 0.469 | 0.469 | 0.349 | 0.273 |
Calculated breaking load | kN | 6.4 | 6.4 | 8.9 | 12.1 | 18.0 | 18.0 | 24.2 | 30.8 |
Street lighting conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
Minimum number of wires | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
Diameter of insulated core | mm | 8.5 | 8.5 | 9.5 | 11.2 | 13.1 | 13.1 | 15.1 | 16.6 |
Max. DC resistance at 20℃ | ohm/km | 1.312 | 1.312 | 0.943 | 0.693 | 0.469 | 0.469 | 0.349 | 0.273 |
Completed cable | |||||||||
Approx. overall diameter | mm | 23.2 | 25.6 | 30.0 | 34.9 | 40.6 | 44.1 | 49.2 | 54.9 |
Approx. weight of cable | kg/km | 470 | 560 | 740 | 980 | 1330 | 1580 | 1940 | 2410 |
Packing length | m/drum | 1000 | 1000 | 1000 | 1000 | 500 | 500 | 500 | 500 |